01/02 AWB8230-1413GB
Electrical connection
41
Actuating the digital inputs
The DF6 has five digital inputs, which are connected internally
with terminal PLC. By default, power is supplied through the
internal 24 V supply. For this purpose, terminals PLC and CM1 are
connected with a jumper. If the digital inputs are to be supplied
from an external source, remove this jumper.
The digital inputs can be operated both with positive (default
setting) and with negative logic. To set it to negative logic, remove
the jumper between terminals PLC and CM1 and connect
terminals PLC and P24 with this jumper. If you are using an
external power supply, you can connect the negative pole (positive
logic) or the positive pole (negative logic) with terminal PLC.
The figure below shows a sample protective circuit for the control
signal terminals
Actuating the digital inputs with
internal supply voltage and
positive logic (default)
Actuating the digital inputs with
internal supply voltage and
negative logic
Actuating the digital inputs with
external supply voltage and
positive logic
Actuating the digital inputs with
external supply voltage and
negative logic
54321CM1PLCP24
54321CM1PLCP24
54321CM1PLCP24
+
–
54321CM1PLCP24
+
–
Figure 34: Control terminal connection (factory setting)
5
FW
P24
H O
L
ZB4-102-KS1
15
M4
PE
2
Cu 2.5 mm
PES
PES
1
2
3
M
R1 REV FWD
4K7
M
F 20 m
efesotomasyon.com - Klockner Moeller - inverter