Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
86
X Program one of the digital inputs 1 to 5 as DB by entering the
value 07 under the corresponding PNU (C001 to C005).
X In PNU A053, enter a delay time t (a fig. 77) from 0 to 5.0 s,
which is to expire before DC braking takes effect after activation
of the DB input.
X Under PNU A054, set a braking force between 0 % and 100 %.
Figure 77: Function chart for DB (DC braking)
f
o
: Output frequency
a Start signal through keypad
FWD/REV
DB
f
O
DB
f
O
a
DB
f
O
a
t