01/02 AWB8230-1413GB
Standard form for user defined
parameter settings
169
A054 DC braking torque on deceleration [%] 0 112
A055 DC braking duration on deceleration [s] 0.0 112
A056 Behaviour on activation of the DB input
• 00: Starts on activation of the input, ends after
PNU A055
• 01: Runs as long as input is active
–01 112
A057 DC braking torque on acceleration [%] 0 112
A058 DC braking duration on acceleration [s] 0.0 113
A059 DC braking frequency [kHz] 5.0 113
A061 Maximum operating frequency [Hz] 0.00 114
A261 Maximum operating frequency (second parameter set) [Hz] 0.00 114
A062 Minimum operating frequency [Hz] 0.00 114
A262 Minimum operating frequency (second parameter set) [Hz] 0.00 114
A063 1. Frequency jump [Hz] 0.00 114
A064 Jump width of the 1st frequency jump [Hz] 0.50 114
A065 2. Frequency jump [Hz] 0.00 114
A066 Jump width of the 2nd frequency jump [Hz] 0.50 114
A067 3. Frequency jump [Hz] 0.00 114
A068 Jump width of the 3rd frequency jump [Hz] 0.50 114
A069 Acceleration pause waiting frequency [Hz] 0.00 115
A070 Acceleration pause waiting duration [s] 0.00 115
A071 PID control
• 00: Inactive
• 01: Active
–00 119
A072 P component of the PID control – 1.0 120
A073 I component of the PID control [s] 1.0 120
A074 D component of the PID control [s] 0.0 120
A075 Setpoint factor of the PID control [%] 1.00 120
A076 Input actual value signal for PID control
• 00: Input OI
• 01: Input O
–00 120
A081 AVR function
• 00: Active
• 01: Inactive
• 02: Inactive during deceleration
–02 128
A082 Motor voltage for AVR function [V] 230/400 128
A085 Energy-saving mode
• 00: Not active
• 01: Active
–00 128
A086 Response time in energy-saving mode [s] 50 128
A092 2. Acceleration time [s] 15.0 73
A292 2. Acceleration time (second parameter set) [s] 15.0 73
A093 2. Deceleration time [s] 15.0 73
A293 2. Deceleration time (second parameter set) [s] 15.0 73
PNU Function Units WE Page Setpoint