02/02 AWB8230-1449GB
Standard form for user defined
parameter settings
11
PNU Meaning Value range Def. Setpoint
b001 Restart mode 00: Fault message
01: 0 Hz start
02: Synchronization to current motor speed and
acceleration
03: Synchronization and deceleration
00
b002 Permissible power failure duration 0.3 to 1.0 s 1.0
b003 Waiting time before restart 0.3 to 1.0 s 1.0
b004 Fault message issued immediately 00: No fault on intermittent mains failure
01: Fault on intermittent mains failure
02: No fault on intermittent mains failure at
standstill and deceleration
00
b005 Number of restart attempts 00: 16 restart attempts
01: Unlimited number of restart attempts
00
b006 Mains phase failure detection 00: Inactive
01: Active
00
b007 Synchronization frequency on return of
mains power
0.00 to 400 Hz 0.00
b012 Tripping current for electronic motor
protection device
0.2 to 1.2 x I
e
[A] I
e
(inverter)
b212 Tripping current for electronic motor
protection device (second parameter set)
0.2 to 1.2 x I
e
[A] I
e
(inverter)
b013 Characteristic for electronic motor
protection device
00: Enhanced protection
01: Normal protection
03: User-definable protection
01
b213 Characteristic for electronic motor
protection device (second parameter set)
00: Enhanced protection
01: Normal protection
03: User-definable protection
01
b015 Frequency 1 for user-definable motor
protection characteristic
0.00 to 400 Hz 0
b016 Tripping current 1 for user-definable
motor protection characteristic
0.0 to 1000 A 0.0
b017 Frequency 2 for user-definable motor
protection characteristic
0.00 to 400 Hz 0
b018 Tripping current 2 for user-definable
motor protection characteristic
0.0 to 1000 A 0.0
b019 Frequency 3 for user-definable motor
protection characteristic
0.00 to 400 Hz 0
b020 Tripping current 3 for user-definable
motor protection characteristic
0.0 to 1000 A 0.0
b021 Motor current limitation 1 00: Inactive
01: Active in every operating status
02: Inactive during acceleration, otherwise active
01
b022 Tripping current 1 for motor current
limitation
0.5 to 1.5 x I
e
[A] I
e
x 1.2
b023 Time constant 1 of motor current
limitation
0.1 to 30 s 1.00
b024 Motor current limitation 2 00: Inactive
01: Active in every operating status
02: Inactive during acceleration, otherwise active
1
b025 Tripping current 2 for motor current
limitation
0.5 to 1.5 x I
e
[A] I
e
x 1.2