Quick Reference Guide
DF6 Frequency Inverter
02/02 AWB8230-1449GB
12
b026 Time constant 2 of motor current
limitation
0.6 to 30 s 1.0
b031 Software dependent parameter
protection
00: Through SFT input; all functions inhibited
01: Through SFT input; function F001 possible
02: Without SFT input; all functions inhibited
03: Without SFT input; function F001 possible
10: Extended parameters adjustable in RUN mode
01
b034 Running time or Mains On time signal 0 to 65530 h 0
b035 Inhibit direction 00: Motor can run in both directions
01: Motor can only run clockwise
02: Motor can only run anticlockwise
00
b036 Voltage ramp to starting frequency 00: Start without voltage reduction.
01: Minimum voltage reduction, approx. 6 ms
...
06: Maximum voltage reduction, approx. 36 ms
06
b037 Display mode 00: All parameters
01: Relevant parameters
02: Parameters saved under PNU U001 to U012
00
b080 Gain factor, analog output AM 0 to 255 180
b081 Gain factor, analog output FM 0 to 255 60
b082 Increased starting frequency
(e.g. with high level of friction)
0.1 to 9.99 Hz 0.50
b083 Pulse frequency 0.5 to 12 kHz 3.0
b084 Initialization causes 00: Clearing the fault history register
01: Selection of default settings
02: Deleting the fault history register and
restoring the default settings
00
b085 Country version 00: Japan
01: Europe
02: USA
01
b086 Frequency factor for display through
PNU d007
0.1 to 99.9 1.0
b087 OFF key 00: Always active
01: Not active with control through the
FWD/REV terminals
00
b088 Motor restart after removal of the
FRS signal
00: At 0 Hz
01: At current motor speed
00
b090 Permissible relative percentage duty
factor for built-in braking transistor
0 to 100 % 0.00
b091 Type of motor stop when Off button is
pressed
00: Braking/deceleration ramp
01: Free run stop (coasting)
00
b092 Configuration of fan operation 00: Fan always switched on
01: Fan switched on only when motor running
00
b095 Enable built-in braking transistor 00: Not enabled
01: Enabled in RUN mode
02: Always enabled
00
b096 Voltage threshold for braking transistor 660 to 760 V 720
b098 Selection of PTC or NTC 00: No temperature monitoring
01: PTC
02: NTC
00
b099 Resistance threshold for thermistor input 0 to 9999 O 3000