Quick Reference Guide
DF6 Frequency Inverter
02/02 AWB8230-1449GB
14
PNU Meaning Value range Def. Setpoint
C001 Function of digital input 1 Function of digital input 1
01: REV, anticlockwise operation
02: FF1, first fixed frequency input
03: FF2, second fixed frequency input
04: FF3, third fixed frequency input
05: FF4, fourth fixed frequency input
06: JOG, jog mode
07: DB, DC braking
08: SET, second parameter set
09: 2CH, second time ramp
11: FRS, controller inhibit
12: EXT, external fault
13: USP, unattended start protection
14: CS, heavy mains starting
15: SFT, parameter protection
16: AT, analog input selection
18: RST, reset
20: STA, three-wire control start signal
21: STP, three-wire control stop signal
22: STA, three-wire control direction
23: PID, activate PID control
24: PIDC, reset integral component of PID control
27: UP, remote access, acceleration
28: DWN, remote access, deceleration
29: UDC, reset frequency with remote control
31: OPE, setpoint value through keypad
32 to 38: Bitwise fixed frequencies
39: OLR, change over current limit
NO: no, no function
18
C002 Function of digital input 2 Values a PNU C001 16
C003 Function of digital input 3 Values a PNU C001 03
C004 Function of digital input 4 Values a PNU C001 02
C005 Function of digital input 5 Values a PNU C001 01
C011 Digital input 1 00: Make contact
01: Break contact
00
C012 Digital input 2 Values a PNU C011 00
C013 Digital input 3 Values a PNU C011 00
C014 Digital input 4 Values a PNU C011 00
C015 Digital input 5 Values a PNU C011 00
C019 Digital input FW Values a PNU C011 00
C021 Signal at relay output K23-K24 00: RUN signal
01: FA1, frequency reached
02: FA2, frequency exceeded
03: OL, Overload
04: OD, PID deviation exceeded
05: AL, fault
06: FA3, frequency reached (1)
08: IP, mains failure, immediate stop
09: UV, undervoltage
11: ONT, mains On time exceeded
12: RNT, running time exceeded
13: THM, motor thermal overload
01
C022 Signal at relay output K33-K34 Values a PNU C021 00
C026 Signal at relay terminals K11-K12 Values a PNU C021 05