Restoring the Default Settings
3
Restoring the Default Settings
Initialization
Two different types of initialization are available:
• Clearing the fault history register
• Restoring the default parameter settings
To delete the fault history register or to restore the default
settings, proceed as follows:
X Make sure that PNU b085 holds the value.
X Under PNU b084 (initialization), enter 00, 01 or 02.
X Press the ENTER key to save the value.
X On the keypad, press both arrow keys and the PRG key at the
same time and keep them pressed.
X While holding the arrow and PRG keys, briefly press the
OFF key.
X Now release all keys again. The display shows d001.
Initialization is now complete.
Country version
Here, you define the country-specific parameter set which will be
loaded during initialization (a PNU b084).
PNU Name Adjustable in RUN mode Value Function Def.
Normal Extended
b084 Initialization – – 00 Clearing the fault history register 00
01 Restoring the default parameter settings (default settings)
02 Deleting the fault history register and restoring the
default settings
PNU Name Adjustable in RUN mode Value Function Def.
Normal Extended
b085 Country
version
– – 00 Japan 01
01 Europe
02 USA