Standard form for user defined
parameter settings
7
Standard form for user defined parameter settings
The DF6 frequency inverters have programmable parameters. For
a detailed description of the parameters, see the specified page in
the manual (AWB8230-1413GB). In the free Setpoint columns
below, you can list the changes you have made from the default
settings.
PNU Meaning Value range Def. Setpoint
A001 Frequency setpoint input 00: Potentiometer
01: Analog inputs O, O2 or OI
02: PNU F001 or A020
03: RS 485 serial interface
04: Optional module in slot 1
05: Optional module in slot 2
01
A002 Start signal definition 01: Input FWD/REV
02: ON key
03: RS 485 serial interface
04: Optional module in slot 1
05: Optional module in slot 2
01
A003 Base frequency 30 to 400 Hz 50
A203 Base frequency (second parameter set) 30 to 400 Hz 50
A004 Maximum end frequency 30 to 400 Hz 50
A204 End frequency (second parameter set) 30 to 400 Hz 50
A005 AT selection 00: AT input switches between analog input O
and OI
01: AT input switches between analog input O
and O2
00
A006 O2 selection 00: O2 signal only
01: Sum of signals at O2 and O/OI without
direction reversal
02: Sum of signals at O2/O or OI with direction
reversal
00
A011 Frequency at minimum setpoint value
(terminal O-L)
0.00 to 400 Hz 0.00
A012 Frequency at maximum setpoint value
(terminal O-L)
0.00 to 400 Hz 0.00
A013 Minimum setpoint value (terminal O-L) 0 to 100 % 0
A014 Maximum setpoint value (terminal O-L) 0 to 100 % 100
A015 Starting frequency (terminal O-L) 00: Apply PNU A011 to motor
01: Apply 0 Hz to motor
01
A016 Analog input filter time constant 1 to 30 8
A019 Fixed frequency selection 00: Binary selection through digital inputs
FF1 to FF4
01: Bitwise selection through digital inputs
SF1 to SF7
00
A020 Frequency setpoint definition PNU A001
must be 02
0.00 to 400 Hz 0.00
A220 Frequency setpoint definition; PNU A001
must be 02 (second parameter set)
0.00 to 400 Hz 0.00