Cables and fuses
The cross-sections of the cables and line protection fuses used
must correspond with local standards. The values are laid out for
three-phase 400 V mains connection.
Use cables with a larger cross-section for supply voltage and motor
cables which exceed about 20 m in length.
Control signal cables should be screenedandscreened and have a
maximum cross-section of 0.14 to 1.5 mm
2
.
Signalling relay output, cross-section of 0.75 to 1.5 mm
2
. Strip
about 5 to 6 mm off the cable ends.
DF6-340-
L1, L2, L3, U, V, W, PE
VDE UL
1)
Moeller mm
2
AWG
11K M32 A 30 A PKM0-25 6 8
15K
M40 A 40 A PKZM4-40 10 6
18K5
M50 A 50 A PKZM4-50 16 6
22K
M50 A 60 A PKZM4-50 25 4
30K
M63 A 70 A PKZM4-63 25 3
37K
M80 A 90 A NZM7-80N-OBI 35 1
45K
M100 A 125 A NZM7-100N-OBI 35 1
55K
M125 A 125 A NZM7-125N-OBI 50 1/0
75K
M160 A 175 A NZM7-160N-OBI 2 x 35 2 x 1
90K
M200 A 200 A NZM7-200N-OBI 2 x 35 2 x 1
110K
M250 A 250 A NZM7-250N-OBI 2 x 50 2 x 1/0
132K
M315 A 300 A NZM7-250N-OBI 2 x 70 2 x 2/0
1) Approved fuses (class J, 600 V) and fuse holders