Mixed Analog Module
15-7
Diagnostic LEDs AO - Voltage mode LED, Current mode LED, Calibration LED
per channel
AI - Overflow and Underflow LED per each input, 24V Plug-in
status LED
The module Overflow and Underflow levels can be configured
to:
Current inputs: ±20mA / 4-20 mA
Voltage inputs: ±5 V / 0-5 V /1-5 V
General - Module error LED
AI Input Isolation 1.5 kV between input and module logic
AI Input Insulation Insulation resistance 100 MΩ @ 500 V DC per IEC60255-5
User Connection 4 Terminal Blocks (3.5mm pitch), Maximum 18 AWG
Cable and TB Holder 40-wire cable braid with Terminal Block holder connector, 26
AWG
Module Replacement Hot swap replacement– module extraction/insertion under
voltage
Operating Voltage 10.8-16 V DC and 3.3 V DC (from the motherboard connector)
Power Consumption
Refer to Appendix D: ACE3600 Maximum Power Ratings.
Dimensions 37 mm W x 225 mm H x 180 mm D (1.5" W x 8.7" H x 7.1" D)
Weight Approx. 0.34 Kg (0.75 Lb)
Specifications subject to change without notice.