Part 12470
Rev. 2 3/25/99
MODE Switch in MOMENTARY and release. Observe current reading retained on
ammeter.
11. Continue to rotate OUTPUT CONTROL knob clockwise while jogging (repeatedly
moving to MOMENTARY position and releasing) OUTPUT MODE Switch until
desired test current is reached. Suggested test current is one and one half times (1.5
x) the rating of the ground fault trip device.
If desired, test current is not reached with OUTPUT CONTROL knob at maximum
clockwise rotation, return knob to zero and transfer output lead to the next higher
voltage/lesser current terminal. Proceed with current adjustment as in Steps 10 and
11 (see SELECTION OF OUTPUT TERMINAL).
12. Put ammeter DISPLAY MODE in NORMAL position.
13. Start test by moving OUTPUT MODE to MAINTAIN position.
14. When device trips, timer stops and output is de-energized. Timer indicates total
elapsed time of the test in seconds or cycles.
15. Turn test set OFF with POWER ON/OFF Switch.
16. Record test results.
IMPORTANT
Refer to manufacturer's instructions for proper test current value and tripping time.