Manual for MVK-MPNIO Modules
18 V 1.9
3. Installation
3.1 Assembly
T
he MVK-MPNIO modules (PP, 7/8”, M23) can be directly mounted to a mounting wall or a ma-
chine. The module is provided with two fixing holes.
T
he MVK-MPNIO PP modules can be directly mounted to a mounting wall or a machine. The
modules are provided with two fixing holes each at the front and at the side.
F
ixing dimensions see Sections 3.1.2 to 3.1.3
The mounting spacing between two modules min. 3 mm (see Fig. 5:
Before attaching the module, it must be assured that the mounting surface is
smooth and flat to prevent mechanical stress in the module housing.
T
he fixing materials required are two M6 screws and two washers to DIN 433 T1/T2. The tight-
ening torque is 8 Nm.
To ensure correct installation and improved heat dissipation we recommend
observing minimum spacing of 3 mm when assembling the MVK-MPNIO
modules.
For angled connectors minimum spacing of 50 mm is required.