Manual for MVK-MPNIO Modules
V 1.9 59
5. Data Modules
The I/O data of the MVK-MPNIO are compiled from a list of virtual data modules.
Virtual head modules Data capacity
Bit
assignment
MVK+ MPNIO DI8 DO8 M23 55264
0
-
MVK+ MPNIO DI8 DI8 POF PP gT 55256
0
-
MVK+ MPNIO DI8 DI8 PP gT 55268
0
-
MVK+ MPNIO DI8 DO8 POF PP gT 55257
0
-
MVK+ MPNIO DI8 DO8 PP gT 55269
0
-
MVK+ MPNIO DIO8(DIO8) PP 55283
0
-
MVK-MPNIO DI8(DI8) 7/8” 55287
0
-
MVK-MPNIO DIO8(DI8) 7/8” 55288
0
-
MVK-MPNIO DIO8(DIO8) 7/8” 55289
0
-
MVK+ MPNIO DI8 DO8 7/8”gT FSU 55339
0
-
Virtual supply module
Data capacity
Bit
assignment
Power supply module
0
-
Virtual user data modules
Data capacity
Bit
assignment
Inputs Pin 4
1 byte
Inputs/diagnostic Pin 2
1 byte
Outputs Pin 4 1 byte
Outputs Pin 2
1 byte
Inputs socket 0..3
1 byte
Inputs socket 4..7 1 byte
Outputs socket 0..3
1 byte
Outputs socket 4..7
1 byte
Virtual diagnostic modules Data capacity Bit
assignment
Peripheral fault socket 1 byte
Sensor supply short-circuit
1 byte
Actuator disable Pin 4
1 byte
Actuator disable Pin 2
1 byte
Actuator warning Pin 4
1 byte
Actuator warning Pin 2
1 byte
Station diagnostics
1 byte
The user data modules are divided into pin-based ( and ) and socket-
based ( and ) modules. If there is a mixed configuration with pin-based
and socket-based modules, the I/O data exchange is blocked and a diagnos-
tic report is generated for the modules affected.