Manual for MVK-MPNIO Modules
V 1.9 59
5. Data Modules
The I/O data of the MVK-MPNIO are compiled from a list of virtual data modules.
Virtual head modules Data capacity
MVK+ MPNIO DI8 DO8 M23 55264
MVK+ MPNIO DI8 DI8 POF PP gT 55256
MVK+ MPNIO DI8 DI8 PP gT 55268
MVK+ MPNIO DI8 DO8 POF PP gT 55257
MVK+ MPNIO DI8 DO8 PP gT 55269
MVK+ MPNIO DIO8(DIO8) PP 55283
MVK-MPNIO DI8(DI8) 7/8” 55287
MVK-MPNIO DIO8(DI8) 7/8” 55288
MVK-MPNIO DIO8(DIO8) 7/8” 55289
MVK+ MPNIO DI8 DO8 7/8”gT FSU 55339
Virtual user data modules
Outputs Pin 4 1 byte
Inputs socket 4..7 1 byte
Virtual diagnostic modules Data capacity Bit
Peripheral fault socket 1 byte
Sensor supply short-circuit
The user data modules are divided into pin-based ( and ) and socket-
based ( and ) modules. If there is a mixed configuration with pin-based
and socket-based modules, the I/O data exchange is blocked and a diagnos-
tic report is generated for the modules affected.