EasyManua.ls Logo

Murr Elektronik MASI65-M12 Series - 4.4 Actuator Connection (Loads); 4.4.1 Pin Arrangement of the Round Plug Connector M12 with Single Signal Assignment; 4.4.2 Pin Arrangement of the Round Plug Connector M12 with Double Signal Assignment

Murr Elektronik MASI65-M12 Series
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MASI65-M12 User's Manual
V 1.1 37
4.4 Actuator connection (loads)
The loads connected to the MASI65-M12 module are supplied by auxiliary power supply.
For MASI65-M12 modules the output voltage is electronically protected against short-circuit and overload.
The max. admissible load on outputs goes from 0,5A to 2A.
The capacity of outputs is indicated in the installation manual of each module.
The module outputs of the MASI65-M12 range and the corresponding
potentials must in no case be galvanic-connected to the inputs or outputs
of other AS-Interface modules
4.4.1 Pin arrangement of the round plug connector M12 with single signal as-
signment
On standard modules the output signal is allocated to pin 4 of the round plug connector M12.
1 2
3
4
5
Fig 4-10 : Pin arrangement of the round plug connector M12 on a standard module
1 : Not allocated
2 : Not allocated
3 : 0 V
4 : Output signal
5 : FE
4.4.2 Pin arrangement of the round plug connector M12 with double signal as-
signment
On modules with double signal assignment (Y wiring) the outputs of the round plug connectors M12 odd
numbers (O1,O3,O5,O7) (pin 4) and pin 2 of the round plug connectors M12 even numbers (O0,O2,O4,O6)
are strapped.
1
2
3
4
5
1 2
3
4
5
Fig. 4-11: Pin arrangement of the round plug connectors M12 with Y wiring
Outputs : O0,O2, O4, O6 Outputs : O1, O3, O5, O7
1 : Not allocated 1 : Not allocated
2 : Output signal O1, O3, O5, O7 2 : Not allocated
3 : 0 V 3 : 0 V
4 : Output signal O0,O2, O4, O6 4 : Output signal O1, O3,O5,O7
5 : FE 5 : FE

Table of Contents

Related product manuals