MASI65-M12 User's Manual
V 1.1 43
7.2 MASI65-M12 product-specific data Standard slaves
7.2.1 MASI65 DI8/0,4A Y 8xM12 Art. No. : 55570
ASI slave IP 67 with 8 digital inputs and Y distribution
Technical data
ASI connection
ASI Bus voltage.................................................................. 26,5…31,6VDC
Reverse polarity protection ................................................ integrated
Profile (code IO/ID/ID2)...................................................... 2 x 0/1/F
Total current usage............................................................ max. 450 mA
Connection (flat cable) ....................................................... ASI standard yellow cable
.......................................................................................... 2x1,5mm² ASI+, ASI-
Inputs
Voltage range..................................................................... 0-30VDC according to IEC1131-2
- Signal 0............................................................................ lin ≤ 2 mA Uin ≤ 5 V
- Signal 1............................................................................ lin ≥ 6 mA Uin ≥ 11 V
Input current....................................................................... ≤ 11 mA
Max. admissible current..................................................... max. 400mA
Short-circuit/overload protection ........................................ integrated
Inputs are galvanic-connected to the ASI bus.
Do not connected them to an auxiliary power supply unit.
Miscellaneous
Temperature range ............................................................ 0...+60 °C
Enclosure type according to DIN 40050............................. IP 67
Weight................................................................................ ~ 160 g
Dimensions ........................................................................ 154x50x38 mm