MASI65-M12 User's manual
44 V 1.1
7.2.2 MASI65-M12 DI4/0,2A DO4/2A Y 8xM12 Art. No : 55 571
ASI slave IP67 with 4 digital inputs, 4 digital outputs TOR and Y distribution
Technical data
ASI connection
ASI Bus voltage..................................................................26,5…31,6VDC
Reverse polarity protection.................................................integrated
Profile (code IO/ID/ID2)......................................................7/F/E
Total current usage ............................................................max. 250 mA
Connection (flat cable)........................................................ASI standard yellow cable
............................................................................................2x1,5mm² ASI+, ASI-
Auxiliary supply
Operating voltage range.....................................................Ub 20 … 30 VDC
Reverse polarity protection.................................................integrated
Connection (flat cable)........................................................ASI standard black cable
............................................................................................2x1,5mm² 24V, 0V
The auxiliary supply must be galvanic-separated according to IEC 364-4-41 (PELV).
Inputs
Voltage range .....................................................................0-30VDC according to IEC1131-2
- Signal 0 ............................................................................lin ≤ 2 mA Uin ≤ 5 V
- Signal 1 ............................................................................lin ≥ 6 mA Uin ≥ 11 V
Input current .......................................................................≤ 11 mA
Max. admissible current .....................................................max. 200mA
Short-circuit/overload protection.........................................integrated
Inputs are galvanic-connnected to the ASI bus.
Do not connect them to an auxiliary supply unit.
Outputs
Max. admissible current .....................................................IL 2 A 50% ED
Total current (max.)............................................................4 A
Output voltage ....................................................................Ub - 0,8V typ.
Switching frequency ...........................................................100 Hz at resistive load
............................................................................................0,2 Hz at inductive load
Short-circuit protection........................................................integrated
Overload protection ............................................................2 A
Miscellaneous
Temperature range.............................................................0...+60 °C
Enclosure type according to DIN 40050.............................IP 67
Weight ................................................................................~ 160 g
Dimensions.........................................................................154x50x38 mm
Nr. E201820 Nr. 32402