MASI65-M12 User's Manual
V 1.1 57
7.2.15 MASI65 DI2/0,2A DO2/2A 4xM12 Art. No : 55625
ASI slave IP67 with 2 digital inputs / 2 digital outputs.
Technical data
ASI connection
ASI Bus voltage.................................................................. 26,5…31,6VDC
Reverse polarity protection ................................................ integrated
Profile (code IO/ID/ID2)...................................................... 3/0/E
Total current usage............................................................ max. 250 mA
Connection (flat cable) ....................................................... ASI standard yellow cable
........................................................................................... 2x1,5mm² ASI+, ASI-
Auxiliary supply
Operating voltage range..................................................... Ub 20 … 30 VDC
Reverse polarity protection ................................................ integrated
Connection (flat cable) ....................................................... ASI standard black cable
........................................................................................... 2x1,5mm² 24V, 0V
The auxiliary supply must be galvanic-separated according to IEC 364-4-41 (PELV).
Inputs
Volgage range.................................................................... 0-30VDC according to IEC1131-2
- Signal 0............................................................................ lin ≤ 2 mA Uin ≤ 5 V
- Signal 1............................................................................ lin ≥ 6 mA Uin ≥ 11 V
Input current....................................................................... ≤ 11 mA
Max. admissible current..................................................... max. 200mA
Short-circuit/overload protection ........................................ integrated
Inputs are galvanic-connected to the ASI bus.
Do not connect them to an auxiliary supply unit.
Outputs
Max. admissible current..................................................... IL 2 A 100% ED
Total admissible current..................................................... 4 A
Output voltage.................................................................... Ub - 0,8V typ.
Switching frequency........................................................... 100 Hz at resistive load
........................................................................................... 0,2 Hz at inductive load
Short-circuit protection....................................................... integrated
Overload protection............................................................ 2 A
Miscellaneous
Temperature range ............................................................ 0...+60 °C
Enclosure type according to DIN 40050............................. IP 67
Weight................................................................................ ~ 100 g
Dimensions ........................................................................ 105x50x38 mm
Nr. E201820 Nr. 32402