Technical Data
User manual 9000-41011-0200000_hdb_en_20 22 / 92
4 Technical Data
4.1 Mico Pro PS (Power Supply)
4.1.1 Electrical data
4.1.1.1 Input
Parameter Conditions Value
Nominal Voltage 100 ... 240 V
Voltage range 90 ... 265 V
Electric strength ≤30 seconds 300 V
Power distribution system TN, TT, IT
DC input operation No
2-phase operation
(phase-to-phase voltage)
Use external fuse for
neutral side
100 ... 240 V
Max. voltage L or N to PE N/A
Nominal frequency 50/60 Hz ±6%
Leakage current N/A
Variants Input: Nominal current, Inrush current, i
2
t, Efficiency
Art.-No. Parameter Conditions Value
9000-41190-0000105 Nominal current 115 V 2.3 A
Nominal current 230 V 1.1 A
Inrush current ≤30 A
i
2
t 1.6 A
2
s
Efficiency 115 V 89,4%
Efficiency 230 V 90,8%
9000-41190-0000110 Nominal current 115 V 3.7 A
Nominal current 230 V 1.7 A
Inrush current ≤25 A
i
2
t 1.6 A
2
s
Efficiency 115 V 91,8%
Efficiency 230 V 93,6%
Fig. 4-1: Art.-No. 9000-41190-0000105 Fig. 4-2: Art.-No. 9000-41190-0000110