Technical Data
User manual 9000-41011-0200000_hdb_en_20 23 / 92
4.1.1.2 Output
Variants Input: Power losses, No-load power losses, Power factor, Start-up volt-
age
Art.-No. Parameter Conditions Value
9000-41190-0000105 Power losses 100% load /115 V 14 W
Power losses 100% load /230 V 12 W
Power losses 50% load /115 V 7 W
Power losses 50% load /230 V 8 W
No-load power losses 115 V 1.2 W
No-load power losses 230 V 1.6 W
Power factor 115 V 0.56
Power factor 230 V 0.50
Start-up voltage 80 V
9000-41190-0000110 Power losses 100% load /115 V 21 W
Power losses 100% load /230 V 16 W
Power losses 50% load / 115 V 10 W
Power losses 50% load / 230 V 8 W
No-load power losses 115 V 1.0 W
No-load power losses 230 V 1.4 W
Power factor 115 V 0.69
Power factor 230 V 0.62
Start-up voltage 85 V
Fig. 4-3: Art.-No. 9000-41190-0000105 Fig. 4-4: Art.-No. 9000-41190-0000110
Parameter Conditions Value
PFC Passive
Internal switching frequency 26 ... 100 kHz
Shutdown undervoltage 65 V
Shutdown overvoltage N/A
Parameter Conditions Value
Parallel connection only 9000-41190-0000110,
max. 2 units
Yes
Nominal output voltage 24 V ±1%
Factory setting 24.1 V ±0.2%
Output voltage range 24 ... 28 V
Output voltage adjustment potentiometer in the
front plate
Dynamic regulation <1ms ±5%
Current - Power Boost 24 V N/A
Current - Power Boost 28 V N/A