Technical Data
User manual 9000-41011-0200000_hdb_en_20 25 / 92
4.1.2 Environmental characteristics
4.1.2.1 Climatic
4.1.2.2 Mechanical
Variants Output: Input failure bridging, Start-up time, Short-circuit current, Out-
put capacitance, Return current when switched-off
Art.-No. Parameter Conditions Value
9000-41190-0000105 Input failure bridging 115 V >20 ms
Input failure bridging 230 V >65 ms
Start-up time 115 V <300 ms
Start-up time 230 V <300 ms
Short-circuit current 7 A
Output capacitance 4070 µF
Return current when
switched-off
27 mA
9000-41190-0000110 Input failure bridging 115 V >44 ms
Input failure bridging 230 V >44 ms
Start-up time 115 V <175 ms
Start-up time 230 V <200 ms
Short-circuit current 15 A
Output capacitance 5270 µF
Return current when
switched-off
30 mA
Parameter Conditions Value
Output rise time 17 ms
Short-circuit energy i
2
t Infinite A
2
s
Extra current / hyper boost No
Max. switchable capacity on the
output
Infinite
Touch Current <0.1 mA
Parameter Conditions Value
Operating temperature -25 ... +55 °C
Operating temperature Art.-Nr. 9000-41190-0000110
@90 ... 160 V
-25 ... +50 °C
Relative humidity no condensation 5 ... 95 %
Storage temperature short-term -40 ... +85 °C
Storage temperature long-term +5 ... +35 °C
Climate class EN 60721 3K3
Climate class EN 60721 3C1
Installation height -500 m ... 2000 m
Art.-No. Parameter Conditions Value
9000-41190-0000105 Vibration test 3 axis, 60 minutes 2-17.8Hz:
±1.6 mm
17.8-500 Hz:
2,0g
Shock test 1 shock/s, 3 axis,
3 pos. & 3 neg. per
axis
15 g / 11ms