Technical Data
User manual 9000-41011-0200000_hdb_en_20 28 / 92
4.1.3 Protection
4.1.3.1 Input protections
4.1.3.2 Recommended Branch Circuit Protections
Tab. 4-1: Art.-No. 9000-41190-0000105
Tab. 4-2: Art.-No. 9000-41190-0000110
4.1.3.3 Output protections
Parameter Conditions Value
Branch circuit protection max. in building installa-
tion
32 A (T)
Overvoltage protection (L ... N) Metal-Oxide-Varistor 300 V / 6 kA
Overvoltage protection (L/N ... PE) N/A
Undervoltage protection Yes, electronic
Variants Input protection: Internal device protection
Art.-No. Parameter Conditions Value
9000-41190-0000105 Internal device
protection
3,15 A (T)
9000-41190-0000110 Internal device
protection
6.3 A (T)
Current
Miniature Circuit Breaker
Neozed fuse or
equivalent
Power Switch
A B C D K gG ≤13 x I
in
2 A ----- - -
4 A - - - - - X X
6 A - - X X X X X
8 A - X X X X X X
10 A XXXXX X X
16 A X X X X X X X
20 A XXXXX X X
24 A X X X X X X X
32 A XXXXX X X
Current
Miniature Circuit Breaker
Neozed fuse or
equivalent
Power Switch
A B C D K gG ≤13 x I
in
2 A ----- - -
4 A - - - - - - -
6 A ----- X X
8 A - - X X X X X
10 A - XXXX X X
16 A X X X X X X X
20 A XXXXX X X
24 A X X X X X X X
32 A XXXXX X X
Parameter Conditions Value
Overload protection (OLP) Yes, autorestart