Technical Data
User manual 9000-41011-0200000_hdb_en_20 29 / 92
4.1.3.4 Output protections with signal connector
4.1.4 Isolation voltages
4.1.4.1 Type testing
4.1.4.2 Routine testing
4.1.4.3 Field testing
Over temperature protection (OTP) Yes, autorestart
Short-circuit protection (OCP) Yes, constant current
Overvoltage protection from device
to load (OVP)
Yes, type 31 V
Overvoltage protection from load to
device
No
Resistance to back feeding loads ≤35 V , autostart
Reverse polarity protection No
Input / Output separation Double or reinforced gal-
vanic isolation
Parameter Conditions Value
Parameter Conditions Value
Overvoltage protection -36 ... +36 V / 600 W
(10/1000 us)
Short-circuit protection N/A
Reverse polarity protection N/A
Overcurrent protection No
Parameter Conditions Value
Input-output 3000 V
Input-PE N/A
Output-PE N/A
Output-Alarm 500 V
Current limit 10 mA
Parameter Conditions Value
Input-output 3000 V
Input-PE N/A
Output-PE N/A
Output-Alarm N/A
Current limit 10 mA
Parameter Conditions Value
Input-output 1750 V
Input-PE N/A
Output-PE N/A
Output-Alarm 500 V
Current limit 10 mA