Technical Data
User manual 9000-41011-0200000_hdb_en_20 34 / 92
4.2.2.3 Electrical safety
4.2.2.4 EMC-interference
4.2.2.5 EMC-immunity
4.2.3 Protection
4.2.3.1 Device protection
4.2.4 Mechanical data
4.2.4.1 Materials
Parameter Conditions Value
Degree of protection EN 60529 IP20
Pollution degree 2
Safe separation External power supply unit SELV/PELV
Overvoltage category III
Insulation voltage
input-output
Type testing / routine check
test
50 V
Parameter Conditions Value
Radio interference field strength
housing
EN 61000-6-3 Industrial and
residual areas
Conducted emission
DC inputs and outputs
EN 61000-6-3 Industrial and
residual areas
Parameter Conditions Value
Electrostatic discharge housing EN 61000-6-2,
EN 61000-4-2
Contact ±4 kV;
air ±8 kV
High-frequency electrical
RF fields housing
EN 61000-6-2,
EN 61000-4-3
80 MHz ... 1.0 GHz:
10 V/m
Fast transients / burst
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Fast transients / burst
signal connections
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Surge voltage
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-5
±0.5 kV DM
Conducted HF
DC connections
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
Conducted HF
control terminals
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
Parameter Conditions Value
Overvoltage protection input Suppressor diode 36 V
Voltage monitoring No
Operating voltage protection EN 61131-1 No
Overload protection No
(only via load circuit moni-
toring)
Parameter Conditions Value
Flame resistance EN 60695-2-1 Low flammability
Housing material Plastic