Technical Data
User manual 9000-41011-0200000_hdb_en_20 42 / 92
4.5 Mico Pro fix module
4.5.1 Electrical data
4.5.1.1 Input
4.5.1.2 Output
Parameter Conditions Value
Operating voltage 12 V , 24 V
Input voltage range 9 V - 30 V
Total operating current continuous
jumper
Plug-In link 40 A
Parameter Conditions Value
Circuit element Static switch
Module initialization time 250 ms
Parallel connection Not possible
Series connection Cascading in 2 steps
(see chapter 7 "Operation")
Disconnecting characteristics accu-
racy
Current 0 % … +20 %
Nominal output voltage Same as input
Turn-on capacity 1 channel, depen-
dent on: component
tolerance, wire
length, used power
supply, load current,
selected current
range
≤30 mF
Variants Output: Number of channels, Tripping current (I
N
), Output current (I
∑
),
Power-up delay
Art.-No. Parameter Conditions Value
9000-41011-0200000,
9000-41011-0400000,
9000-41011-0600000,
9000-41011-0800000,
9000-41011-1000000,
9000-41011-1600000
Number of channels 1
9000-41012-0200000,
9000-41012-0400000,
9000-41012-0600000
Number of channels 2
9000-41014-0200000,
9000-41014-0400000,
9000-41014-0600000
Number of channels 4
9000-41011-0200000 Tripping current (I
N
) Full load 2 A (+20%)
9000-41011-0400000 Tripping current (I
N
) Full load 4 A (+20%)
9000-41011-0600000 Tripping current (I
N
) Full load 6 A (+20%)
9000-41011-0800000 Tripping current (I
N
) Full load 8 A (+20%)
9000-41011-1000000 Tripping current (I
N
) Full load 10 A (+20%)
9000-41011-1600000 Tripping current (I
N
) Full load 16 A (+20%)
9000-41012-0200000 Tripping current (I
N
) Full load per channel 2 A (+20%)
Output current (I
∑
) Full load all channels 4 A
Power-up delay Per channel to avoid
inrush current peaks
75 ms