Technical Data
User manual 9000-41011-0200000_hdb_en_20 50 / 92
4.6 Mico Pro fix CL2 module
4.6.1 Electrical data
4.6.1.1 Input
4.6.1.2 Output
Parameter Conditions Value
Operating voltage 12 V , 24 V
Input voltage range 9 V - 30 V
Total operating current continuous
jumper
Plug-In link 40 A
Parameter Conditions Value
Circuit element Static switch
Module initialization time 250 ms
Parallel connection Not possible
Series connection Cascading in 2 steps
(see chapter 7 "Operation")
Disconnecting characteristics accu-
racy
Current 0 % … +9 %
Nominal output voltage Same as input
Turn-on capacity Until SW 1.01;
1 channel, depen-
dent on: component
tolerance, wire
length, used power
supply, load current,
selected current
range
≤20 mF
Turn-on capacity 1 channel, depen-
dent on: component
tolerance, wire
length, used power
supply, load current,
selected current
range
≤30 mF
Variants Output: Number of channels, Tripping current (I
N
), Output current (I
),
Power-up delay
Art.-No. Parameter Conditions Value
9000-41011-0400001 Number of channels 1
Tripping current (I
N
) Full load 3 ... 4 A
(+9%)
9000-41014-0400001 Number of channels 4
Tripping current (I
N
) Full load per channel 3 ... 4 A
(+9%)
Output current (I
) Full load all channels 16 A
Power-up delay Per channel to avoid
inrush current peaks
75 ms