Technical Data
User manual 9000-41011-0200000_hdb_en_20 52 / 92
4.6.1.3 Performance record
All efficiencies and voltage drops at 50% load.
4.6.2 Environmental characteristics
4.6.2.1 Climatic
Characteristics: Disconnecting characteristics | Tripping current (I
N
)
For Mico Pro fix Tripping current (I
N
) 2 A to 10 A
Disconnection time at short circuit: approx. 5 ms
Fig. 4-16: Disconnecting characteristics | Tripping current
Article Art.-No. Efficiency Voltage drop per
channel
Mico Pro fix 1.4 CL2 9000-41011-0400001 96,6 % 0,06 V
Mico Pro fix 4.4 CL2 9000-41014-0400001 96,6 % 0,06 V
Parameter Conditions Value
Relative humidity 5 ... 85 %
Storage temperature -40 ... +80 °C
Climate class IEC/EN 60721-3-3 3K3
Surrounding air temperature
range (T
a
)
-25 ... +55 °C
Variants installation height
Art.-No. Conditions Value
9000-41011-0400001 Above sea level, without any
restrictions
-500 m ... 6000 m
9000-41014-0400001