Technical Data
User manual 9000-41011-0200000_hdb_en_20 54 / 92
4.6.2.5 EMC-immunity
4.6.3 Protection
4.6.3.1 Device protection
4.6.4 Mechanical data
4.6.4.1 Materials
4.6.4.2 Mounting data
Parameter Conditions Value
Fast transients / burst
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Fast transients / burst
signal connections
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Surge voltage
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-5
±0.5 kV DM
Electrostatic discharge housing EN 61000-6-2,
EN 61000-4-2
Contact ± 4 kV; air ± 8 kV
Conducted HF
DC connections
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
Conducted HF
control terminals
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
High-frequency electrical
RF fields housing
EN 61000-6-2,
EN 61000-4-3
80 MHz ... 1.0 GHz: 10 V/m
Parameter Conditions Value
Short circuit protection Short circuit-proof
Overvoltage protection input Suppressor diode 36 V
Overvoltage protection output Suppressor diode 36 V
Overload protection See Disconnecting charac-
teristics
Voltage monitoring No
Safety fuse variants: Internal fuse (Fail-Safe-Element), per channel
Art.-No. Designation Tripping current Fuse
9000-41011-0400001 Mico Pro fix 1.4
CL2
4 A Safety fuse
4 A (T) time-lag fuse
9000-41014-0400001 Mico Pro fix 4.4
CL2
4 A Safety fuse
4 A (T) time-lag fuse
Parameter Conditions Value
Flame resistance EN 60695-2-1 Low flammability
Housing material Plastic
Parameter Conditions Value
Dimension Depth (D) 114 mm
Dimension Height with unlocking actua-
tor (H)
130 mm
Dimension Height without unlocking
actuator (H2)
111 mm
Dimension Mounting (a) 55.5 mm