Technical Data
User manual 9000-41011-0200000_hdb_en_20 57 / 92
4.7 Mico Pro flex module
4.7.1 Electrical data
4.7.1.1 Input
4.7.1.2 Control input
4.7.1.3 Output
Parameter Conditions Value
Operating voltage 12 V , 24 V
Input voltage range 9 V ... 30 V
Total operating current continuous
jumper
Plug-In link 40 A
Parameter Conditions Value
CTRL input voltage Low 0 V … 1 V,
high 9 V … 30 V
CTRL control current High ≤6 mA
CTRL signal Ctrl functions 2 & 3
are available from
software version
1.06a onwards.
(XXXXXX-X.XX-
1.06a)
1 | OFF: "high" 40±3 ms
ON: "high" 20±3 ms
2 | OFF: "high" 400±30 ms
ON: "high" 200±30 ms
3 | OFF: "high" >600 ms,
ON: "high" CTRL & ON
>500 ms
CTRL switching frequency Max. 10 Hz
CTRL overvoltage protection Suppressor diode 36 V
Remote switch-on (ON) Possible
ON input voltage Low 0 V … 1 V,
high 9 V … 30 V
ON control current High ≤6 mA
ON pulse length 0 V and pulse ON: "high" 120 ms
ON overvoltage protection Suppressor diode 36 V
Parameter Conditions Value
Circuit element Static switch
Module initialization time 250 ms
Parallel connection Not possible
Series connection Cascading in 2 steps (see
chapter Operation)
Disconnecting characteristics accu-
racy
Current 0 % … +20 % (-5% ...
+15%)
Nominal output voltage Same as input
Turn-on capacity 1 channel, depen-
dent on: component
tolerance, wire
length, used power
supply, load current,
selected current
range
≤30 mF