Technical Data
User manual 9000-41011-0200000_hdb_en_20 60 / 92
4.7.1.4 Control output
4.7.1.5 Performance record
All efficiencies and voltage drops at 50% load.
4.7.2 Environmental characteristics
4.7.2.1 Climatic
Parameter Conditions Value
Output voltage terminal "Alarm" Channel off 0 V
Output voltage terminal "Alarm" Channel on Input voltage
Current terminal "Alarm" ≤20 mA
Parameter Conditions Value
Output voltage terminal "90 %" Channel with output current
≤90 % trigger current
0 V
Output voltage terminal "90 %" Channel with output current
≤90 % trigger current
Input voltage
Current terminal ≤20 mA
Article Art.-No. Efficiency Voltage drop per
channel
Mico Pro flex 1.10 9000-41091-0101000 99,8 % 0,04 V
Mico Pro flex 1.20 9000-41091-1102000 99,6 % 0,09 V
Mico Pro flex 2.10 9000-41092-0101000 99,6 % 0,09 V
Mico pro flex 4.10 9000-41094-0101000 99,3 % 0,16 V
Parameter Conditions Value
Relative humidity 5 ... 85 %
Storage temperature -40 ... +80 °C
Climate class IEC/EN 60721-3-3 3K3
Variants Installation height
Art.-No. Parameter Conditions Value
9000-41091-0101000,
9000-41091-1102000,
9000-41092-0101000,
9000-41094-0101000
Installation height Above sea level,
without any restric-
tions
-500 m ... 2000 m
9000-41091-0101000,
9000-41092-0101000
Installation height Above sea level,
max. 8 A tripping cur-
rent full load per
channel
2000 m ... 4000 m
9000-41091-0101000,
9000-41092-0101000
Installation height Above sea level,
max. 6 A tripping
current full load per
channel
4000 m ... 6000 m
9000-41091-1102000 Installation height Above sea level,
max. 16 A tripping
current full load per
channel
2000 m ... 4000 m
9000-41091-1102000 Installation height Above sea level,
max. 12 A tripping
current full load per
channel
4000 m ... 6000 m