Technical Data
User manual 9000-41011-0200000_hdb_en_20 63 / 92
4.7.2.5 EMC-immunity
4.7.3 Protection
4.7.3.1 Device protection
4.7.4 Mechanical data
4.7.4.1 Materials
4.7.4.2 Mounting data
Parameter Conditions Value
Fast transients / burst
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Fast transients / burst
signal connections
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Surge voltage
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-5
±0.5 kV DM
Electrostatic discharge housing EN 61000-6-2,
EN 61000-4-2
Contact ± 4 kV; air ± 8 kV
Conducted HF
DC connections
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
Conducted HF
control terminals
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
High-frequency electrical
RF fields housing
EN 61000-6-2,
EN 61000-4-3
80 MHz ... 1.0 GHz: 10 V/m
Parameter Conditions Value
Short circuit protection Short circuit-proof
Overvoltage protection input Suppressor diode 36 V
Overvoltage protection output Suppressor diode 36 V
Overload protection See Disconnecting charac-
teristics
Voltage monitoring No
Safety fuse variants: Internal fuse (fail-safe element), per channel
Art.-No. Designation Tripping current Fuse
9000-41091-0101000 Mico Pro flex 1.10 1 A ... 10 A Fast-blow safety fuse
15 A (F)
9000-41091-1102000 Mico Pro flex 1.20 11 A ... 20 A Fast-blow safety fuse
30 A (F)
9000-41092-0101000 Mico Pro flex 2.10 1 A ... 10 A Fast-blow safety fuse
15 A (F)
9000-41094-0101000 Mico Pro flex 4.10 1 A ... 10 A Fast-blow safety fuse
15 A (F)
Parameter Conditions Value
Flame resistance EN 60695-2-1 Low flammability
Housing material Plastic
Parameter Conditions Value
Dimension Depth (D) 114 mm
Dimension Height with unlocking actuator (H) 130 mm
Dimension Height without unlocking actuator
(H2)
111 mm