Installation
User manual 9000-41011-0200000_hdb_en_20 76 / 92
6.3 Connecting cable
6.3.1 Mico Pro PS (power supply)
NOTE
The connection cables must be approved for the following operating tempera-
tures:
≥75 ºC
6.3.2 Mico Pro PM (power module)
NOTE
The connection cable at the INPUT terminals (+ 24V, GND/0V) must be ap-
proved for the following operating temperatures:
≥75 ºC with surrounding air temperature ≤40 °C
≥90 ºC with surrounding air temperature 40 °C ... 55 °C
6.3.3 Mico Pro fix and flex
For Mico Pro fix and flex modules with 1 A to 16 A tripping current
NOTE
The connection cable at the OUTPUT terminals (OUT, GND/0V) must be ap-
proved for the following operating temperatures:
≥75 ºC with surrounding air temperature ≤50 °C
≥90 ºC with surrounding air temperature 50 °C ... 55 °C
For Mico Pro flex modules with 11 A to 20 A tripping current
NOTE
The connection cable at the terminals must be approved for the following op-
erating temperatures:
≥90 ºC with surrounding air temperature ≤50 °C