EasyManua.ls Logo

Murr Elektronik Mico Pro Series - Control and signals

Murr Elektronik Mico Pro Series
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
User manual 9000-41011-0200000_hdb_en_20 83 / 92
7.4 Control and signals
7.4.1 Mico Pro PS / Mico Pro PM
The control and diagnostic functions described on the Mico Pro PS (power
supply) / Mico Pro PM (power module) are group signals from or for the entire
Mico Pro system (Mico Pro PS / Mico Pro PM with added system compo-
nents). If Mico Pro PS (Art.-No. 9000-41190-0000110) is used in parallel
mode, signals are available only on the power supply next to the Mico Pro
channels.
ON terminal
(restart)
control input
Signal for control via a PLC
ATTENTION:
- If a consumer circuit (channel) is disconnected manually using the "ON/
OFF" button, it can only be reconnected manually by means of the "ON/
OFF" button .
- If a consumer circuit (channel) is disconnected via the "CTRL" terminal, it
can only be reconnected via the "CTRL" terminal .
ON signal level: "low" (0 V ... 1 V DC)
ON signal level: "high" (9 V ... 30 V DC), min. 120 ms
Consumer circuits disconnected due to overload can be reconnected with
this signal.
Control input
CTRL terminal
Signal for control via a PLC
ATTENTION:
- If a consumer circuit (channel) is disconnected manually using the "ON/
OFF" button, it can only be reconnected manually by means of the "ON/
OFF" button .
- If a consumer circuit (channel) is disconnected via the "CTRL" terminal, it
can only be reconnected via the "CTRL" terminal .
CTRL signal: "low" (0 V ... 1 V DC)
CTRL signal: "high" (9 V ... 30 V DC), 40±3 ms / 400±30 ms,
Consumer circuits (channels) are disconnected.
CTRL signal: "high" (9 V ... 30 V DC), 20±3 ms / 200±30 ms,
Consumer circuits (channels) are connected.
CTRL signal: "high" (9 V ... 30 V DC), >600 ms,
Consumer circuits (channels) are disconnected.
CTRL signal: "high" (9 V ... 30 V DC), CTRL&ON >500 ms,
Consumer circuits (channels) are connected.
Control output
Alarm 13, 14
Terminals
Potential-free
Terminal contact group signal output max. 30 V AC/DC, 20 mA
Alarm contact: contact closed
All consumer circuits (channels) in the system are connected.
Alarm contact: contact open
At least one channel in the system is disconnected.
Control output
90% 23, 24
Terminals
Potential-free
Terminal contact group signal output max. 30 V AC/DC, 20 mA
90% contact: contact closed
A load of >90% of the tripping current is measured on at least one consum-
er circuit (channel) in the system.
90% contact: contact open
All consumer circuits (channels) in the system are measured with a load
of <90% of the tripping current.

Table of Contents