Operation
User manual 9000-41011-0200000_hdb_en_20 84 / 92
7.4.2 Mico Pro fix
Group signals can be used via the Mico Pro power module (power feeding
module). These functions are described in the manual of the Mico Pro power
module.
7.4.3 Mico Pro flex
Group signals can be used via the Mico Pro power module (power feeding
module). These functions are described in the manual of the Mico Pro power
module.
ON terminal
(restart)
control input
Signal for control via a PLC
ATTENTION:
- If a consumer circuit (channel) is disconnected manually using the "ON/
OFF" button, it can only be reconnected manually by means of the "ON/
OFF" button .
- If a consumer circuit (channel) is disconnected via the "CTRL" terminal, it
can only be reconnected via the "CTRL" terminal .
ON signal level: "low" (0 V ... 1 V DC)
ON signal level: "high" (9 V ... 30 V DC), min. 120 ms
Consumer circuits disconnected due to overload can be reconnected with
this signal.
Control input
CTRL terminal
Signal for control via a PLC
ATTENTION:
- If a consumer circuit (channel) is disconnected manually using the "ON/
OFF" button, it can only be reconnected manually by means of the "ON/
OFF" button .
- If a consumer circuit (channel) is disconnected via the "CTRL" terminal, it
can only be reconnected via the "CTRL" terminal .
CTRL signal: "low" (0 V ... 1 V DC)
CTRL signal: "high" (9 V ... 30 V DC), 40±3 ms / 400±30 ms,
Consumer circuits (channels) are disconnected.
CTRL signal: "high" (9 V ... 30 V DC), 20±3 ms / 200±30 ms,
Consumer circuits (channels) are connected.
CTRL signal: "high" (9 V ... 30 V DC), >600 ms,
Consumer circuits (channels) are disconnected.
CTRL signal: "high" (9 V ... 30 V DC), CTRL&ON >500 ms,
Consumer circuits (channels) are connected.
Control output
Alarm terminal
Signal output signal for connection to PLC inputs
Alarm signal level: "high" U
in
/ 20 mA
When the consumer circuit (channel) is connected.
Alarm signal level: "low" 0 V DC
When the consumer circuit (channel) is disconnected.
Control output
90-% terminal
Signal output signal for connection to PLC inputs
90-% signal level: "high" U
in
A load of >90 % of the tripping current is measured on the consumer circuit
(channel).
90-% signal level: "low" 0 V DC
A load of <90 % of the tripping current is measured on the consumer circuit
(channel).