6.1.3.8. DIO8(DIO8) Art.-No. 55309
Bus data
Transfer protocol ................................................ Profibus-DP acc. to DIN 19245
Transfer rates ..................................................... 9,6/19,2/45,45/93,75/187,5/500/
............................................................................ 1500/3000/6000/12000 kBaud
Baud rate detection ............................................ automatically
Operating modes ................................................ Sync- and freeze mode are supported
Addressing ......................................................... 1 99 via BCD rotary switch
ID number ........................................................... 0x064A hex
Supply
Operating voltage U
B
.......................................... 24 V
Supply voltage range ......................................... 18 ... 30 V
Current consumption (without inputs) ................ 150 mA
Sensor supply .................................................... 200 mA per sensor
Short-circuit protection for sensors .................... Multifuse,
............................................................................ up to 100 mA load automatic start
............................................................................ from 100 mA load reset required
Tripping time multifuse ....................................... 1s at I
K
1 A and 23°C
Reverse polarity protection inputs ...................... Yes
Inputs / diagnostics
Max. no. of inputs ................................................ 16
Delay time with signal change ........................... 2 … 5 ms
Input characteristic ............................................. EN 61131-2, type 2
Input filter............................................................. approx. 1 ms
Over voltage protection ....................................... Yes (suppressor diode)
Reverse polarity protection
Module electronics .............................................. Yes
Sensors ............................................................... No
Actuators ............................................................. No
Outputs
Max. no. of outputs .............................................. 16
Nominal current ................................................... 1.6 A
Max. total current ................................................ 9 A
Over voltage protection ....................................... Yes (suppressor diode)
Cable length ........................................................ 0.75 mm²10 m
............................................................................ 0.34 m5 m
Cable diameter .................................................... 1.5 mm²
Signal delay ......................................................... 2 5 ms
Max. switching frequency at resistive load .......... 20 Hz
Max. lamp load .................................................... 10 W