Technical Data
User manual 59719_hdb_en_12 20 / 65
4.2 Art.-No. 59819
4.2.1 Electrical data
Total current US
Fig. 4-2: Total current US
Module supply
Operating voltage US 24 V
Operating voltage range US 18 ... 30 V
Total current US ≤50 °C (see Derating) ≤4 A
Power consumption when idling ≤40 mA
Galvanic isolation No
0
0,5
I [A]
1
2,5
1,5
2
-30
0
T [°C]
-10 2010
3
30
-20
40 50 60 70
IO-Link
Communication speed COM3
Transfer rate 230,400 bit/s
Bus protocol IO-Link V1.1.2, compati-
ble with IO-Link V1.1.3
IO-Link cycle time ≥1 ms
VendorID 0x012F
DeviceID 0x0C000A
Process data 4 byte (inputs),
2 byte (outputs)
Sensor power supply
Connection/female connector M12
Operating voltage 24 V
Power supply Per port ≤0.5 A
Input (DI)
Connection/female connector M12
Cable cross section ≤0.75 mm²
Cable length ≤30 m
Input characteristic EN 61131-2 Type 1 + Type 3
Input filter 1 ... 10 ms, adjustable