Hot water 1 temperatures
Adjustable is the maximum permitted temperature to be reached at the my-PV temperature sensor
(factory setting = 60 °C). This has nothing to do with a bimetal thermostat which may be installed!
If the cut out temperature of an immersion heating element with a bimetal thermostat is set
too low, the AC•THOR may possibly be unable to reach the desired temperature!
If the optional automatic temperature boost backup is shown "On" in the window on the right
(factory setting "Off"), a minimum temperature can then be set (factory setting 50 °C).
Automatic temperature boost backup "On":
The AC•THOR can ensure a minimum temperature at the my-PV temperature sensor with the upper
heater. This is supplied with maximum power.
Hot water 1 min switching times
This setting can be selected when the temperature boost backup is "On" under Hot water 1
temperatures".
There are two time windows available to maintain the minimum temperature on the my-PV
temperature sensor. Start and finish can each be defined at full hours. Factory settings suggest
switching times of 5 to 11 pm and 5 to 7 am.
TIP: Restrict the times when the minimum temperature has to be maintained to
mornings and evenings, to increase your own PV consumption through the day!
Start hour and stop hour refer to the same calendar day. If a time window is defined over
midnight, hot water backup will not start!
If the adjusted start-hour is after the stop-hour, hot water backup will not start!
Hot water 1 min weekdays
This setting can be selected when the temperature boost backup is "On" under Hot water 1
temperatures".
You can select the weekdays on which the minimum temperature has to be maintained. In the
factory settings, all weekdays are activated.