FP2/FP2SH CPU COM. port
GT10
FP2/FP2SH communication format settings
System register no. Item Value Set
412
Selection of target use of RS232C port Computer link
413
Data length 8 bits
Parity check Yes
Parity setting Odd
Stop bits 1 bit
Line return code CR
Start code No STX
414
Baud rate setting 19200 bits/s
415
Unit number 1
416
Modem connection No connection
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no. Wire color Dot mark
1 Brown Black dot
2 Brown Red dot
3 Yellow Black dot
4 Yellow Red dot
5 Green Black dot
6-- --
7 Green Red dot
8-- --
9-- --
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting to the FP2/FP2SH COM. port
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6 N.C.
7
8
9
N.C.
ER
SD SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side GT main unit side
Pin no.Pin no.
Abbreviation
Abbreviation