ISSUE 4.0 SL2100
INSTALLING THE MAIN & EXPANSION CHASSIS 56
Figure 2-25 ETH Lug
• The grounding cable is supplier-provided.(not attached to the system)
Each chassis in the system must be grounded separately using the procedure listed below.
1. Loosen the screw.
2. Insert a grounding wire (user supplied).
3. Tighten the screw.
4. Connect the grounding wire to earth ground.
Proper grounding is very important to protect the system from external
noise and to reduce the risk of electrocution in the event of a lightning
strike.
1.8.2 AC Power Requirement
A dedicated 100V-120V/220V/230V/240V 50/60Hz circuit located within two meters of the Chassis is
required. A separate dedicated AC outlet is necessary for each Chassis.
Double Pole/Neutral Fusing
(Power supply fuses are located at both the L and N side.)