FlexPAK 800/1000
19
EN
NOTE! Ensure that the room where the unit is installed is well venlated.
It is recommended that the unit is posioned indoors.
Under some condions, the unit may draw air directly into the high-pressure fan. This may
cause a dangerous underpressure in the room if air cannot enter freely. There are to be two
openings for venlaon, at least 250×250 mm (10"×10") in size. One is to be placed up high
and the other one down low.
The warm exhaust air is to be directed from the unit and out of the premises, see gure 9,
item 4. Connect a duct that directs the exhaust air outdoors.
The air can be directed to a heat exchanger, but there are not to be any dampers which
may obstruct the air ow.
5.4.2 Outdoor installaon
If installed outdoors, consider the following:
• The area needs to be protected from the weather. Cover the top of the unit to protect
it from snow, rain or falling debris.
•
The ambient temperature is not to be below 0 °C (32 °F) or exceed 40 °C (104 °F). If
the ambient temperature will less or greater than these limits, contact Nederman for
more informaon about de-rang.
5.4.3 Moving the unit
WARNING! Risk of personal injury.
• Use proper liing and protecve equipment.
• Be careful not to let the unit p over to avoid a crush risk.
• The unit is to be anchored to the oor, parcularly if it is located at a high level, to
ensure that it does not move and fall down. The frame has four holes for anchoring.
Take care during relocaon and transport of the unit to avoid pping. If the unit is to
be moved, the frame is to be aached to the front of the boom frame, see gure 10,
item 1.
If the unit is to be moved, the frame is to be aached to the front of the boom frame, see
gure 10, item 1.
5.5 Electrical installaon
WARNING! Risk of electric shock.
• Work with electric equipment is to be carried out by a qualied electrician.
• The connected wiring system is to be electrically connected to the Potenal Equalizing
System (PES) on the premises.
NOTE! The electrical connecon is NOT to be equipped with an earth leakage circuit
breaker when the frequency converter is provided with an EMC lter. The EMC lter
funcon will make the earth leakage circuit breaker shut o power.
NOTE! In accordance with the European standard, the incoming 3-phase supply is to
be ed with a hand-operated disconnecng device that conforms to the demands on
disconnectors. The disconnecng device is to be ed within 2–3 m from FlexPAK 800/1000
and be clearly visible from the unit. Refer to local and naonal standards when located
outside of Europe.
NOTE! Check the connuity of the protecve current circuit before the unit is used.