If the command fails, contact Customer Support.
If the
Key Manager type = onboard and the Restored column = anything other than yes/true,
use the security key-manager onboard sync command to re-sync the Key Manager type.
Use the security key-manager key query to verify that the
Restored column = yes/true for all
authentication keys.
11. Connect the console cable to the partner node.
12. Give back the node using the storage failover giveback -fromnode local command.
13. Restore automatic giveback if you disabled it by using the storage failover modify -node local -auto
-giveback true command.
Return the failed part to NetApp - AFF A900
After you replace the part, you can return the failed part to NetApp, as described in the RMA instructions
shipped with the kit. Contact technical support at
NetApp Support, 888-463-8277 (North America), 00-800-44-
638277 (Europe), or +800-800-80-800 (Asia/Pacific) if you need the RMA number or additional help with the
replacement procedure.
Chassis
Replace the chassis - AFF A900
Before you begin
To replace the chassis, you must remove the power supplies, fans, controller modules,
I/O modules, DCPM modules, and USB LED module from the impaired chassis, remove
the impaired chassis from the equipment rack or system cabinet, install the replacement
chassis in its place, and then install the components into the replacement chassis.
All other components in the system must be functioning properly; if not, you must contact technical support.
About this task
You can use this procedure with all versions of ONTAP supported by your system.
This procedure is disruptive. For a two-node cluster, you will have a complete service outage and a partial
outage in a multi-node cluster.
Shutdown the impaired controller - AFF A900
You must shut down the node or nodes in the chassis prior to moving them to the new
chassis.
About this task
If you have a cluster with more than two nodes, it must be in quorum. If the cluster is not in quorum or a
healthy node shows
false for eligibility and health, you must correct the issue before shutting down the
impaired node; see the
Administration overview with the CLI.
If AutoSupport is enabled, suppress automatic case creation by invoking an AutoSupport message:
system node autosupport invoke -node * -type all -message
MAINT=number_of_hours_downh
38