20
Backlight control
Backlight on (default)
Backlight off
22
Beeps while primary
source is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit
will transfer to line
mode if overload occurs
in battery mode.
Bypass disable (default)
Bypass enable
25
Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
1KVA default setting: 14.1V
2KVA/3KVA/3KW default setting: 28.2V
5KW default setting: 56.4V
If self-defined is selected in program 5, this program can be set up.
Setting range is from 12.5V to 15.0V for 1K model, 25.0V to 30.0V for
2KVA model, 25.0V to 31.5V for 3KVA/3KW
model
and
48.0V to
V
for 5KW
model.
Increment of each click is 0.1V.
27
Floating charging
voltage
1KVA default setting: 13.5V
2KVA/3KVA/3KW default setting: 27.0V
5KW default setting: 54.0V
If self-defined is selected in program 5, this program can be set up.
Setting range is from 12.5V to 15.0V for 1K model, 25.0V to 30.0V for
2KVA model, 25.0V to 31.5V for 3KVA/3KW
model
and
48.0V to
61.0V
for 5KW
model. Increment of each click is 0.1V.
61.0
20