1KW default setting: 10.5V
3KW default setting: 21.0V
5KW default setting: 42.0V
If self-defined is selected in program 5, this program can be set up.
Setting range is from 10.5V to 12.0V for 1K model, 21.0V to 24.0V for
3KW
Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to
setting value no matter what percentage of load is connected.
30
Battery equalization
Battery equalization disable (default)
If “Flooded” or “User-Defined” is selected in program 05, this program
can be set up.
31
Battery equalization
voltage
1KW default setting: 14.6V
3KW default setting: 29.2V
5KW default setting: 58.4V
Setting range is from 12.5V to 15.0V for 1KW model,
60min (default)
Setting range is from 5min to
900min. Increment of each click
is 5min.
Battery equalized timeout
120min (default)
Setting range is from 5min to
900 min. Increment of each click
is 5 min.
30days (default)
Setting range is from 0 to 90
days. Increment of each click is
1 day
21