MENU 5.7 - START GUIDE
When the control module is started for the first time the
start guide starts automatically. Start it manually here.
See page 30 for more information about the start guide.
MENU 5.8 - QUICK START
It is possible to start the compressor from here.
Caution
There must be a heating, cooling or hot water
demand to start the compressor.
NOTE
Do not quick start the compressor too many
times over a short period of time, as this could
damage the compressor and its surrounding
equipment.
MENU 5.9 - FLOOR DRYING FUNCTION
length of period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2 days
Factory setting, period 4: 3 days
temp. period 1 – 7
Setting range: 15 – 70 °C
Default value:
20 °Ctemp. period 1
30 °Ctemp. period 2
40 °Ctemp. period 3
45 Ctemp. period 4
40 °Ctemp. period 5
30 °Ctemp. period 6
20 °Ctemp. period 7
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven periods
are to be used, set the remaining period times to 0 days.
Mark the active window to activate the underfloor drying
function. A counter at the bottom shows the number of
days the function has been active.
TIP
If operating mode "add. heat only" is to be used,
select it in menu 4.2.
TIP
It is possible to save a floor drying log that
shows when the concrete slab has reached
the correct temperature. See section "Logging
floor drying" on page 45.
MENU 5.10 - CHANGE LOG
Read off any previous changes to the control system
here.
The date, time and ID no. (unique to certain settings)
and the new set value is shown for every change.
Caution
The change log is saved at restart and remains
unchanged after factory setting.
MENU 5.11 - HEAT PUMP SETTINGS
Settings for installed heat pump can be made in the
submenus.
MENU 5.11.1.1 - HEAT PUMP
Make settings for the installed heat pump here. To see
what settings you can make, see installation manual for
the heat pump.
41Chapter 8 | ControlNIBE SMO 20