MENY 5.3.12 - EXHAUST/SUPPLY AIR
MODULE
months btwn filter alarms
Setting range: 1 24
Default value: 3
lowest extract air temp.
Setting range: 0 10 °C
Default value: 5 °C
bypass at excess temperature
Setting range: 2 10 °C
Default value: 4 °C
bypass during heating
Setting range: on/off
Factory setting: off
cut-out value, exh. air temp.
Setting range: 5 30 °C
Default value: 25 °C
max. fan speed
Setting range: 0 100%
Factory setting: 75 %
min. fan speed
Setting range: 0 100%
Factory setting: 60 %
control sensor 1 (HTS)
Setting range: 1 4
Default value: 1
months btwn filter alarms: Set how often the filter alarm
is to be displayed.
lowest extract air temp.: Set the minimum extract air
temperature to prevent the heat exchanger freezing.
bypass at excess temperature: If a room sensor is in-
stalled, set the excess temperature at which the bypass
damper is to open here.
TIP
See the installation instructions for ERS and
HTS for a function description.
MENU 5.3.14 - F135
charge pump speed
Setting range: 1 100 %
Factory setting: 70 %
hot water at cooling
Setting range: on/off
Factory setting: off
Here you can set the charge pump speed for F135. You
can also choose whether you want to be able to charge
hot water with F135 at the same time as the outdoor
module produces cooling.
Caution
It is necessary for “active cooling 4 pipe” to
be selected in either “accessories” or “soft
in/outputs” to enable activation of “hot water
during cooling”. The heat pump must also be
activated for cooling operation.
MENU 5.3.15 - GBM COMMUNICATION
MODULE
start diff additional heat
Setting range: 10 2,000 DM
Factory setting: 700 DM
hysteresis
Setting range: 10 2,000 DM
Factory setting: 100 DM
Make settings for the gas boiler GBM 10-15 here. For
example . you can select when the gas boiler is to start.
See the accessory installation instructions for a descrip-
tion of function.
MENU 5.3.16 - HUMIDITY SENSOR
climate system 1 HTS
Setting range: 1–4
Default value: 1
limit RH in the room, syst.
Setting range: on/off
Factory setting: off
prevent condensation, syst.
Setting range: on/off
Factory setting: off
limit RH in the room, syst.
Setting range: on/off
Factory setting: off
NIBE VVM 225Chapter 8 | Control Menus54