This sets the start optimizer speed in mm/s
2
. This feature can help to overcome starting stiction for elevators installed with a motor gearbox, or for
systems installed with guide rail pads rather than rollers, or in retro fit applications where imperfections in the guide rails result in reduced starting
performance. A request to release / open the brake in Open loop control mode using start optimization will not be carried out unless the start optimizer
speed is reached, consider the rated slip for the motor when adjusting the speed level for the start optimizer. The start optimizer speed is also used
on start up for the brake release delay.
A61 (Start Optimizer Enable G45)
When set to Off (0) the start optimizer is disabled.
When set to On (1) the start optimizer is enabled.
This feature can help to overcome starting stiction for elevators installed with a motor gearbox, or for systems installed with guide rail pads rather than
rollers, or in retro fit applications where imperfections in the guide rails result in reduced starting performance. A request to release / open the brake
in Open loop control mode using start optimization will not be carried out unless the start optimizer speed is reached, consider the rated slip for the
motor when adjusting the speed level for the start optimizer. The start optimizer speed is also used on start up for the brake release delay.
A62 to A80 (User defined parameters for User menu A)
Parameter A62 through to A80 are User menu A parameters which can be set-up by the user for quick access to parameters which are required for
the specific application. Menu Z set-up configuration allows all parameters required to simply be routed from the advanced menu’s to parameters A29
through to A80.
Example:
Menu Z set-up configuration User menu A
Parameter Z01 Parameter A01
Enter: Configured to:
Z01 = User Security Status (H02) A01 = User Security Status (H02)
A61 {G45} Start Optimizer Enable
RW Bit US
OL
Ú Ö
RFC-A
Off (0) or On (1) Off (0)
RFC-S
Time
Speed
A60 (Start Optimizer Speed G46)
A59 (Start Optimizer Jerk G47)
A35 (Run Jerk 1 G13)
A58 (Start Optimizer Time G48)
A74 to A80 User Defined Parameters For User Menu A
OL
ÚÖ
RFC-A
RFC-S