8.1 Menu B: Motor
Menu B Motor allows the user to setup the Elevator motor parameters from the motor data sheet or the motor nameplate.
In addition to the standard motor nameplate details Menu B Motor also allows additional features to be setup for the Elevator motor control:
• Motor nameplate details • Motor auto tune selection and results
• Motor operating PWM level, lifetime control • System current limit and motor thermal protection
• Rotation of motor output phases, U, V, W through a single bit parameter • Drive output motor contactor control and monitoring
• Quasi square wave operation • Deadtime compensation
• Sensorless operation parameters
Parameter
Range(Ú)Default(Ö)
Type
Open-Loop RFC-A RFC-S Open-Loop RFC-A RFC-S
B01 Drive Control Mode Open-loop (1), RFC-A (2), RFC-S (3) RW Txt ND NC PT
B02 Motor Rated Current ±VM_RATED_CURRENT A Maximum Heavy Duty Rating RW Num RA US
B03 Motor Rated Voltage ±VM_AC_VOLTAGE_SET V
200V drive: 230 V, 400V drive: 400 V
575V drive: 575 V, 690V drive: 690 V
RW Num RA US
B04 Motor Rated Power Factor 0.000 to 1.000
0.850 RW Num RA US
B05
Open-Loop: Number Of Motor
Poles
Automatic (0) to
240 Pole Pairs
Automatic (0)
Poles
RW Txt US
RFC-A: Number Of Motor
Poles
Automatic
(0) to 240
Pole Pairs
Automatic (0)
Poles
RW Txt US
RFC-S: Number Of Motor
Poles
Automatic (0) to 240
Pole Pairs
16 (8) Poles RW Txt US
B06 Motor Rated Frequency 0.0 to 550.0 Hz
50 Hz: 50Hz, 60 Hz: 60 Hz RW Num US
B07 Motor Rated Speed 0 to 33000 rpm 0.00 to 33000.00 rpm
50 Hz : 1500 rpm
60 Hz : 1800 rpm
50 Hz:
1450 rpm
60 Hz:
1750 rpm
3000.00 rpm RW Num US
B09
Open-Loop: Open Loop
Control Mode
Ur S (0),
Ur (1),
Fixed (2),
Ur Auto (3),
Ur I (4),
Ur I (4) RW Txt US
RFC-S: Phasing Test On
Enable
Disabled (0),
Short (1),
Short Once (2),
Long (3),
Long Once (4)
Disabled (0) RW Txt US
B10 Slip Compensation Enable Off (0) or On (1)
On (1) RW Bit US
B11 Motor Autotune
None (0)
Static (1)
Rotating (2)
None (0),
Static (1),
Rotating (2),
Inertia 1 (3),
Inertia 2 (4)
None (0), Static (1),
Rotating (2),
Inertia 1 (3),
Inertia 2 (4),
Full Stationary (5)
None (0) RW Num NC
B12 Low Frequency Voltage Boost 0.0 to 25.0 %
3 % (Frame 6)
2 % (Frame 7 to 8)
1 % (Frame 9E to Frame 11E)
RW Num US
B13
Maximum Switching
Frequency
0 to VM_SWITCHING_FREQUENCY kHz 8 kHz (4) RW Txt RA US
B14
Minimum Switching
Frequency
0 to VM_MIN_SWITCHING_FREQUENCY kHz 3 kHz (1) RW Txt US
B15
Switching Frequency Step
Size
1 to 2 2 RW Num US
B16 Symmetrical Current Limit ±VM_MOTOR1_CURRENT_LIMIT % 165.0 %
175.0 %
RW Num RA US
B17
Percentage Over Current Trip
Level
10 (0), 20 (1), 30 (2), 40
(3), 50 (4), 60 (5), 70
(6), 80 (7), 90 (8),
100 (9) %
100 % (9) RW Txt US
B18 Motor Percentage Flux
0.0 to
150.0 %
RO Num ND NC PT
B19 Thermal Protection Mode
0 = Motor trip. 1 = Motor Limit, 2 = Drive limit,
3 = Both limit, 4 = Disabled
0 - Motor trip RW Bin US
B20
Motor Thermal Time Constant
1
1.0 to 3000.0 s 89.0 s RW Num US
B21
Motor Protection Accumulator
Power-up Value
Power down (0), Zero (1), Real time (2) Power down (0) RW Txt US
B22
Motor Thermal Time Constant
2
1.0 to 3000.0 s 89.0 s RW Num US
B23
Motor Thermal Time Constant
2 Scaling
0 to 100 % 0 % RW Num US
B24
Rated Iron Losses As
Percentage Of Losses
0 to 100 % 0 % RW Num US
B25
Motor Parameter Adaptive
Control
0 to 2 0 RW Num US