F40 T5 T6 Analog Input 1 Invert Off (0) or On (1) Off (0) RW Bit US
F41 Analog Input 1 Destination A00 to AN99 G35 RW Num DE PT US
F42 T5 T6 Analog Input 1 Offset ±100.00 % 0.00 % RW Num US
F43 T5 T6 Analog Input 1 Minimum ±100.00 % -100.00 % RW Num US
F44
T5 T6 Analog Input 1
Maximum
±100.00 % 100.00 % RW Num US
F45 T7 Analog Input 2 Mode
4-20mA Low (-4), 20-4mA Low (-3),
4-20mA Hold (-2), 20-4mA Hold (-1),
0-20mA (0), 20-0mA (1), 4-20mA Trip (2),
20-4mA Trip (3), 4-20mA (4), 20-4mA (5),
Volt (6)
Volt (6) RW Txt US
F46 T7 Analog Input 2 Scaling 0.000 to 10.000 1.000 RW Num US
F47 T7 Analog Input 2 Invert Off (0) or On (1) Off (0) RW Bit US
F48 T7 Analog Input 2 Destination A00 to AN99 G33 RW Num DE PT US
F49 T7 Analog Input 2 Offset ±100.00 % 0.00 % RW Num US
F50 T7 Analog Input 2 Minimum ±100.00 % -100.00 % RW Num US
F51 T7 Analog Input 2 Maximum ±100.00 % 100.00 % RW Num US
F52 T8 Analog Input 3 Mode
Volt (6), Therm Short Cct (7), Thermistor (8),
Therm input (9)
Thermistor input RW Txt US
F53 T8 Analog Input 3 Scaling 0.000 to 10.000 1.000 RW Num US
F54 T8 Analog Input 3 Invert Off (0) or On (1) Off (0) RW Bit US
F55 T8 Analog Input 3 Destination A00 to AN99 A00 RW Num DE PT US
F56 T8 Analog Input 3 Offset ±100.00 % 0.00 % RW Num US
F57 T8 Analog Input 3 Minimum ±100.00 % -100.00 % RW Num US
F58 T8 Analog Input 3 Maximum ±100.00 % 100.00 % RW Num US
F59
T8 Analog Input 3 Thermistor
Type
DIN44082 (0), KTY84 (1), PT100 (4W) (2),
PT1000 (4W) (3), PT2000 (4W) (4),
2.0mA (4W) (5), PT100 (2W) (6),
PT1000 (2W) (7), PT2000 (2W) (8),
2.0mA (2W) (9)
DIN44082 (0) RW Txt US
F60
T8 Analog Input 3 Thermistor
Trip Threshold
0 to 5000 3300 RW Num US
F61
T8 Analog Input 3 Thermistor
Reset Threshold
0 to 5000 1800 RW Num US
F62
T8 Analog Input 3 Thermistor
Feedback
0 to 5000
RO Num ND NC PT
F63
T8 Analog Input 3 Thermistor
Temperature
-50 to 300 °C
RO Num ND NC PT
F64 T9 Analog Output 1 Source A00 to AN99 A00 RW Num PT US
F65 T9 Analog Output 1 Scaling 0.000 to 10.000 1.000 RW Num US
F66 T9 Analog Output 2 Source A00 to AN99 A00 RW Num PT US
F67 Analog Output 2 Scaling 0.000 to 10.000 1.000 RW Num US
F68 Start Speed Selection Filter ±200 ms 20 ms RW Num US
F69 Encoder Thermistor Type
DIN44082 (0), KTY84 (1), 0.8 mA (2),
Encoder (3)
DIN44082 (0) RW Txt US
F70
Encoder Thermistor Trip
Threshold
0 to 5000 3300 RW Num US
F71
Encoder Thermistor Reset
Threshold
0 to 5000 1800 RW Num US
F72 Encoder Thermistor Feedback 0 to 5000
RO Num ND NC PT
F73
Encoder Thermistor
Temperature
-50 to 300 °C
RO Num ND NC PT
F74 Motor Thermistor Input Select
No Thermistor (0), T8 Analog IP 3 (1),
Encoder D Type (2)
T8 Analog IP 3 (1) RW Num US
RW Read / Write RO Read-only Bit Bit parameter Txt Text string Date Date parameter Time Time parameter
Chr Character parameter Bin Binary parameter IP IP address Mac MAC address Ver Version number SMP
Slot, menu,
parameter
Num Number parameter DE Destination ND No default value RA Rating dependent NC Non-copyable PT Protected
FI Filtered US User save PS Power-down save
Parameter
Range(Ú) Default(Ö)
Type