30 Installation and System Design Guide
Issue Number: 1
Table 2-35 Size 11E emission compliance
Key (shown in decreasing order of permitted emission level):
E2R EN 61800-3:2004 second environment, restricted distribution (Additional measures may be required to prevent interference)
E2U EN 61800-3:2004 second environment, unrestricted distribution
I Industrial generic standard EN 61000-6-4:2007
EN 61800-3:2004 first environment restricted distribution (The following caution is required by EN 61800-3:2004)
R Residential generic standard EN 61000-6-3:2007
EN 61800-3:2004 first environment unrestricted distribution
EN 61800-3:2004 defines the following:
The first environment is one that includes residential premises. It also includes establishments directly connected without intermediate
transformers to a low-voltage power supply network which supplies buildings used for residential purposes.
The second environment is one that includes all establishments other than those directly connected to a low-voltage power supply network which
supplies buildings used for residential purposes.
Restricted distribution is defined as a mode of sales distribution in which the manufacturer restricts the supply of equipment to suppliers,
customers or users who separately or jointly have technical competence in the EMC requirements of the application of drives.
IEC 61800-3:2004 and EN 61800-3:2004
The 2004 revision of the standard uses different terminology to align the requirements of the standard better with the EC EMC Directive.
Power drive systems are categorized C1 to C4:
Note that category 4 is more restrictive than E2R, since the rated current of the PDS must exceed 400 A or the supply voltage exceed 1000 V, for the
complete PDS.
Motor cable
length (m)
Switching Frequency (kHz)
3 4 6 8 12 16
Using internal filter:
10 - 50
C3
100
C3 C4
Using external filter:
20
C2
100
C2 C3
This is a product of the restricted distribution class according to IEC 61800-3. In a residential environment this product may cause radio
interference in which case the user may be required to take adequate measures.
Category Definition
Corresponding code used
above
C1 Intended for use in the first or second environments R
C2
Not a plug-in or movable device, and intended for use in the first environment only
when installed by a professional, or in the second environment
I
C3 Intended for use in the second environment, not the first environment E2U
C4
Rated at over 1000 V or over 400 A , intended for use in complex systems in the
second environment
E2R
CAUTION