Before Release to Passenger Operation
42-02-7223 C1 4-63
4
iControl DC
Before Release to Passenger Operation
Danger
Before the elevator can be turned over to normal passenger use, it is important that no safety func-
tion or circuit remains bypassed. Items to check include, but are not limited to:
All safety switches set to the OFF position
No jumper between SB and 3 (iBox)
No jumper between SAFH and 3 (iBox)
Learn and Fault/Function switches set to OFF (iBox)
No jumper between Gov and 3 (iBox)
Pattern Scaling set to 100% (Pattern screen/Common tab)
Note
If this is a local car (part of a group), the “Car identifier” parameter, on the Configuration >
General > General tab, must be set so that the Group controller can identify the car to which it is
communicating. Initially the Car identifier is defaulted to 1. The Car Identifier range is from 1 to
15. The Car identifier for each car in a Group must be unique (no duplicates).