NE200/300 Series Drive User Manual
114 Chapter 6 Parameter description
This parameter defines the waiting time before restart and over-voltage
reset delay time.
F1.18
Rotational speed tracking
direction inspection
0~10
F1.19
Rotational speed tracking
direction inspection time
10~1000ms
50ms
F1.18 and F1.19 only for NE300.
F1.18 is for selecting whether the rotational speed tracking direction
inspection is valid.
0: Disable 1: Enable
Notes for F1.19:
The motor start method is the DC brake mode while the motor
frequency is below 2Hz, and the set value of DC brake current and
brake time is not zero. The motor start method is normal from the
zero frequency if the set value of the DC brake current and brake
time is zero.
6.3 Auxiliary running function group (F2)
F2.00 Jog running freq. Range: 0.0~50.005.00Hz
F2.01 Jog Acc. time
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
F2.02 Jog Dec. time
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
These parameters define the frequency and Acc/Dec time of the JOG
operation. In JOG operation, the drive starts according to starting mode 0
(F1.00=0 direct start) and stops according to stopping mode 0 (F1.08=0
Deceleration to stop). The Jog acceleration time refers to the time the drive